P799 Communications Control
Enables the read/write access to parameters via remote communications.
Primary Index
Values

Echo Processing (P800 to P807)

P800 Near Blanking
The space near the transducer face which cannot be measured.
Primary Index
Values
Related
Use this feature if the surface is reported to be near the transducer face but is in fact
much further away. Extend this value when changing transducer location, mounting, or
aiming.
Please note that changing the Near Blanking cannot correct measurement problems.
Ensure that Span (P007) < Empty (P006) minus Near Blanking (P800)
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
Protocol
(Index 1 controls the Modbus Master (RS-485 or RS-232); Index 2
controls the Fieldbus Master (PROFIBUS DP , DeviceNet, or Allen
Bradley Remote I/O)
0
Read Only
1
*
Read/Write
Restricted Access – read only except for P799 which is
2
read/write
Single Point Model
Global
Range: 0.000 to 9999
Preset:
0.300m (Most transducers)
0.450m (XCT-8, XCT-12)
P006 Empty
P007 Span
P833 TVT Start Min
Dual Point Model
Transducer
Page 199