Pump Control
Setting a Pump Down Group
Example: Sewage Wet Well
Setting a group of three pumps to pump down a wet well.
Inflow
Set the Common Parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Parameter
P001
P002
P003
P004
P005
P006
P007
1.
Example assumes a single measurement unit. If your MultiRanger has
dual point software installed then some parameters are indexed by two.
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
P006
P007
1
Value Description
Index
G
1
Operation = level
G
1
Material = liquid
G
2
Maximum Process Speed = medium
G
102
Transducer = XPS-10
G
1
Units = meters
G
1.8
Empty = 1.8m
G
1.4
Span = 1.4m
MultiRanger
Outflow
Page 57