Open Channel Monitoring (OCM)
[MR 200]
An OCM installation is defined one of three ways, based on the Primary Measuring
Device (PMD):
1.
Dimensional (P600 = 2,3,6,7)
For some common weir and flume types. PMD dimensions (P602) are entered directly.
•
BS-3680 / ISO 1438/1 Thin plate V notch weir on page 74
•
BS-3680 / ISO 4359 Rectangular Flume on page 75
•
Palmer Bowlus Flume on page 76
•
H Flume on page 77
2.
Exponential (P600 = 1)
For most other weir and flume types. PMD exponents provided by the manufacturer are
entered. Flow is calculated using the exponent (P601) and the maximum values (P603 and
P604).
•
Standard Weirs on page 78
•
Parshall Flume on page 79
•
Leoplod Lagco on page 80
•
Cut Throat Flume on page 81
3.
Universal (P600 = 4,5)
For all other PMDs, the head-to-flow curve can be plotted based on known breakpoints,
usually supplied by the PMD manufacturer.
•
Typical Flow Characterization on page 82
•
Example Flumes on page 83
•
Example Weirs on page 83
Common Parameters
These Quick Start parameters are required for all installations.
Parameter
P001
P002
P003
P004
P005
P006
P007
P801
Page 72
MultiRanger 100/200 – INSTRUCTION MANUAL
Index
Value Description
G
6
Operation
G
1
Material
G
2
Max. Process Speed
G
102
Transducer
G
1
Units
G
1.8
Empty
G
1.0
Span
G
0.8
Range Extension to avoid LOE
= OCM
= liquid
= medium
= XPS-10
= meters
= 1.8m
= 1.4m
7ML19981FB05