P213 mA Output Max Limit
Sets the maximum mA output value (in mA) to be produced.
Primary Index
Values
Related

mA Output Trim (P214 to P215)

This does not affect the P203 value shown, and is used when recalibration of an external
device is impractical.
To adjust the value so that the device correctly indicates 4.00 (when P214 is accessed) or
20.00 mA (when P215 is accessed):
1.
Attach ammeter to HydroRanger 200 mA output.
2.
Access P214, Index 1 (for mA output 1) or 2 (for mA output 2). Press CLEAR and
ENTER
3.
Enter the exact value displayed on the ammeter into P214 (Index 1 or 2).
4.
The ammeter should then read exactly 4.00 mA.
5.
Repeat steps 1 to 4 to set P215, using 20 mA as the desired value.
P214 4 mA Output Trim
Calibrates the 4 mA output.
Primary Index
Values
Related
Adjust this value so the device indicates 4.000 mA when P214 is accessed.
P215 20 mA Output Trim
Calibrates the 20 mA output.
Primary Index
Values
Related
Adjust this value so the device indicates 20.00 mA when P215 is accessed.
Page 150
MultiRanger 100/200 – INSTRUCTION MANUAL
mA output
Range: 0.000 to 22.00
Preset: 20.2 mA
P200 mA Output Range / P212 mA Output Min LImit
. The ammeter should show a value near 4 mA.
mA output
Range: 0 to 9999
P215 20 mA Output Trim
mA output
Range: 0 to 16000
P214 4mA Output Trim