mA Output Failsafe (P219) [MR 200]

Please note that this parameter applies to the MultiRanger 200 only.
P219 mA Output Failsafe [MR 200]
Use for failsafe operation, independent of the Failsafe Material Level (P071).
Primary Index
Values
Related
Selecting an independent mA Failsafe option:
1.
Press MODE
2.
Press ARROWS
3.
Press ENTER
Or, to produce an mA output at a specific value, enter the value required. This is used only
if mA output is allocated to a transducer (P201 = 1 to 7).

mA Input (P250 to P260) [MR 200]

Please note that these parameters apply to the MultiRanger 200 only.
P250 mA Input Range [MR 200]
Shows the mA input range of the connected mA device.
Primary Index
Values
Ensure this range corresponds to the output range of the external device. All level
measurements will equate % of Span with the % of the mA range.
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
mA output
Range: 0.000 to 22.00
OFF
*
mA output responds to Failsafe Material Level (P071).
last known value is held until normal operation
HOLd
resumes
LO
produce the Empty mA output immediately
HI
produce the Span mA output immediately
P201 mA Output Function
to display the Auxiliary Function symbol.
to scroll access the failsafe options.
when the desired option displayed.
Global
1
0 to 20 mA
2
*
4 to 20 mA