Word Order (R40,062); Map Id (R40,063) - Siemens MAG 1100 Operating Instructions Manual

Electromagnetic flowmeters
Table of Contents

Advertisement

Type
Description
Point
Temperature (2)
Data
Totalizer for points 1
and 2 [MR 200]
Discrete Inputs (2)
Relay Outputs (3 or
I/O
6)
mA Input (1)
[MR 200]
mA Output (2)
Pump on Setpoint (3
or 6)
Pump off Setpoint (3
Pump
or 6)
Control
Pumped Volume (2)
[MR 200]
Pump Hours (3 or 6) 41,450
Pump Starts (3 or 6) 41,470
Parameter Access
1.
Maximum registers shown; fewer may be used depending on options installed.
The MultiRanger was designed to make it easy for master devices to get useful
information via Modbus. This chart gives an overview of the different sections. A more
detailed explanation of each section follows below.

Word Order (R40,062)

This determines the format of unsigned, double-register integers (UINT32).
0 indicates that the most significant word (MSW) is given first
1 indicates that the least significant word (LSW) is given first
Unsigned Double Precision Integer (UINT32)
See
Additional information is available from our Web site at www.siemens.com/
Note:
processautomation

Map ID (R40,063)

This value identifies the register map used by the MultiRanger. See
Location
on page 96.
Parameter Access (R43,998 – R46,999)
See also
Page 98
MultiRanger 100/200 – INSTRUCTION MANUAL
1
Start
#R
41,030
2
41,040
4
41,070
1
41,080
1
41,090
1
41,110
2
41,420
6
41,430
6
41,440
4
12
6
43,998 to 46999
on page 107 for more information.
on page 102 for details.
Read/
Data Type
Write
–50 to 150
R
UINT32
R/W
Bit Mapped
R
Bit Mapped
R/W
0000 to
R
20,000
0000 to
R/W
20,000
0000 to
R/W
10,000
0000 to
R/W
10,000
UINT32
R
UINT32
R
0000 to
R
10,000
R/W
P782 Parameter Index
7ML19981FB05

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mag 1100 fMag 3100Mag 3100 pMag 5100 wMag 5000Mag 6000

Table of Contents