Level System Synchronization

The MultiRanger 100/200 CANNOT be synchronized with the MultiRanger
Note:
Plus or the HydroRanger.
When using multiple ultrasonic level monitors, be sure to run the transducer cables in
separate grounded metal conduits.
When separate conduits are not possible, synchronize the level monitors so that no unit
transmits while another is waiting for echo reception.
Synchronizing with another MultiRanger 100/200, or other Siemens Milltron-
ics instruments (DPL+, SPL, XPL+, LU 01, LU 02, LU 10, Hydro+, EnviroRanger,
MiniRanger):
Mount the level monitors together in one cabinet
Use a common power (mains) supply and ground (earth) for all units
Interconnect the SYNC terminals of all level monitors
Contact Siemens Milltronics or your local distributor. Go to
www.siemens.com/processautomation.

Power

Important!
Before applying power to the MultiRanger for the first time, ensure any connected
alarm/control equipment is disabled until satisfactory system operation and
performance is verified.
Notes for AC power connections
The equipment must be protected by a 15 A fuse, or circuit breaker in the
building installation.
A circuit breaker or switch in the building installation, marked as the disconnect
switch, must be in close proximity to the equipment and within easy reach of the
operator.
Note: Make sure unit is
connected to a
reliable ground.
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
Other Siemens
Milltronics Transceiver
Ground
MultiRanger
GND
L1
L2/N
Page 19