Status Parameters

Status parameters give the operating status of the MultiRanger. You can access
parameters with the hand programmer (see page 31) or with Dolphin Plus (see page 26).
Remote SCADA system access is also possible.
Parameter
P203
mA Output Value
P254
Scaled mA Input Value
[MR 200 only]
P275
Scaled Discrete Input Value Shows current value of discrete input,
P322
LCD Total Low
[MR 200 only]
P323
LCD Total High
[MR 200 only]
P341
Run Time
P342
Start Ups
P664
Temperature
P707
Rate Value
P708
Volume Rate Display
[MR 200 only]
P729
Scan Time
P806
Echo Strength
P920
Reading Measurement
P921
Material Measurement
P922
Space Measurement
P924
Volume Measurement
[MR 200 only]
P925
Flow Measurement (OCM) Current flow value, if OCM programmed
[MR 200 only]
P926
Head Measurement (OCM) Current level, if OCM programmed
[MR 200 only]
P927
Distance Measurement
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
Values
0 to 22 – Current mA output
0 to 9999 – Current mA input after scaling
values vary by DI function
The last four digits of the totalizer
The first four digits of the totalizer
The number of days the MultiRanger has
been operating
The number of times power has been
cycled
Current temperature measured by
transducer
Current rate of material level change
Current rate of material volume change
Seconds since last level scan
Strength of primary echo
Current primary reading
Current level from P007–Span
Empty space above the material level
Current volume value, if programmed
Distance from transducer face to material
Page 23