P320 Flow Max [MR 200]
View the highest flow rate calculated (in units or %).
Primary Index
Values
Related
P321 Flow Min [MR 200]
View the lowest flow rate calculated (in units or %).
Primary Index
Values
Related

LCD Totalizer (P322 and P323) [MR 200]

Please note that these parameters apply to the MultiRanger 200 only.
Use these features to view, reset, or preset the eight-digit display totalizer when
Operation is set for OCM or Pumped Volume (P001 = 6 or 7). The eight-digit totalizer is
divided into two groups of four digits. The four least significant totalizer digits are stored
in P322, and the four most significant digits are stored in P323. Adjust these values
separately to set a new total.
Example
P323 = 0017
P322 = 6.294
Totalizer Display = 00176.294
Totalizer units are dependent upon programming. Enter zero 0 (if required) to reset the
totalizer to zero. Alternatively, enter any other (applicable) value, to preset the totalizer to
the necessary value.
A second point is available only if the Dual Point Feature is enabled.
Note:
Page 158
MultiRanger 100/200 – INSTRUCTION MANUAL
Single Point Model
Global
Range: -999 to 9999 (view only)
P604 Maximum Flow
Single Point Model
Global
Range: -999 to 9999 (view only)
P604 Maximum Flow
Dual Point Model
Transducer
Dual Point Model
Transducer
7ML19981FB05