Parameter
Use PTs: PT primary
Use PTs: PT secondary
Prim. nom.
Current Inputs
Use CTs?
Use CTs: CT primary
Use CTs: CT secondary
Use CTs: Separate CT In?
Separate CT In?
CT Primary In
Zero-Point Suppression
Zero-point suppression
(in % of Vrated and Irated)

Binary Inputs

2.2.3
2.2.3.1

Function Description

The device has 2 binary inputs.
11
Separate CT In is available only if the following Connection type is selected: 3P4W (four-wire, any load).
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020
Default Setting
AC 10 000 V
AC 100 V
230.00 V
No
(no checkmark)
AC 1000.00 A
AC 1.00 A
No (no checkmark)
11
AC 1000.00 A
0.3 %
2.2 Setting Process Connections and Other Settings
Setting Range
AC 100.0 V to 1 000 000.0 V
AC 1.0 V to 460.0 V
AC 57.7 V to 400 V (autorange)
IEC 61000-4-30 Class A:
Up to AC 230 V:
200 % overvoltage
> AC 230 V to 400 V:
200 % to 15 % overvoltage
UL conditions:
Up to AC 170 V:
200 % overvoltage
> AC 170 V to 300 V:
200 % to 15 % overvoltage
Yes (checkmark)
No (no checkmark)
AC 1.00 A to 100 000.00 A
AC 1.00 A to 10.00 A
Yes (checkmark)
No (no checkmark)
AC 1.00 A to 100 000.00 A
0.0 % to 10.0 %
Device Functions
47