General Appendix E: Updating Software; Updating Software - Siemens MAG 1100 Operating Instructions Manual

Electromagnetic flowmeters
Table of Contents

Advertisement

General Appendix E: Updating Software

Updating Software

To update the software in the MultiRanger, please contact your Siemens Milltronics
representative to obtain the software. For a complete list of representatives, go to
www.siemens.com/processautomation.
WARNINGS:
1. All parameter values will be lost during software upgrade.
Record your current parameters manually or using Dolphin Plus
before upgrade.
2. Disable all pumps and alarms before updating software, as
relays can change state during the software update causing pumps
to turn on or off .
To install the software, please complete the following:
1.
Connect your PC or laptop to the MultiRanger RJ-11 RS-232 port.
2.
Run the .exe Downloader program in the software. Use this to set the RS-232
settings to match your MultiRanger. Please note that the software default settings
will already match the default settings of the unit. Changes are only necessary if the
RS-232 settings in the unit have been changed.
3.
Complete the Downloader program steps.
4.
Verify that Downloader confirms a succesful upgrade before exiting.
5.
Complete a Master Reset (P999) after a successful upgrade, before re-entering
parameters.
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
Page 245

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mag 1100 fMag 3100Mag 3100 pMag 5100 wMag 5000Mag 6000

Table of Contents