P110 Level Source
Sets the level source on which the indexed relay is assigned to a measurement point.
Please note that Difference and Average settings are MultiRanger 200 features
Primary Index
Values
Altered by:

MultiRanger 200

Please note that these features are only available on the MultiRanger 200.
In Single Point Mode (standard):
Points 2 and 3 are available only if Operation is set for difference or average
(P001 = 4 or 5).
In Dual Point Mode (optional):
Point 2 is always available, and Point 3 is available only if Operation is set for difference or
average (P001 = 4 or 5).
P111 Relay Control Function
Sets the control algorithm used to trip the relay.
Please note that parameter P111 values vary between the MultiRanger 100 and the
MultiRanger 200.
Primary Index
Values
Altered by
Use zero 0 (preset) to disable control of the indexed relay.
All relay ON/OFF points must be referenced from Empty (P006), regardless
Note:
of Operation Mode selection (POO1).
Page 134
MultiRanger 100/200 – INSTRUCTION MANUAL
Relay
Range: 1 to 3
1
* Point # 1 = Transducer One
2
Point # 2 = Transducer Two
3
Point # 3 = Difference (P001=4) or Average (P001=5)
[MR 200]
[MR 200]
P003 Maximum Process Speed
P700 Max Fill rate
P701 Max Empty rate
P070 Failsafe Timer
P071 Failsafe Material Level
Relay
See chart below
P100 Preset Applications
.
7ML19981FB05