Relays
Relays are the primary controls of external devices such as pumps or alarms.
The MultiRanger comes with extensive control and alarm functions.
General Introduction
Depending on the model, up to six onboard multi-purpose relays are provided on the
MultiRanger. Each relay may be independently assigned to one function and has a
corresponding status icon on the LCD.
The relay functions fall under three modes of operation:
Mode
alarm
pump
miscellaneous
Relay Function
The MultiRanger 100 or 200 can be programmed with relays that may not
Note:
be installed, depending on the model. To determine the number of relays in your
MultiRanger 100 or 200, open the lid and count the large white relays to the left of
the display.
Alarm
Level
In high alarm, the function goes on when the level rises to the ON setpoint and goes off
when the level lowers to the OFF setpoint. In low alarm, the function goes on when the
level lowers to the ON setpoint and goes off when the level rises to the OFF setpoint.
In Bounds [MR 200]
The relay will be in alarm if the level is inside the zone between the setpoints.
Out of Bounds [MR 200]
The relay will be in alarm if the level is outside the zone between the setpoints.
Rate of Change [MR 200]
In filling alarm, the function goes on when the rate of filling increases to the ON setpoint
and goes off when the rate of filling drops to the OFF setpoint. In emptying alarm, the
function goes on when the rate of emptying increases to the ON setpoint and goes OFF
when the rate of emptying drops to the OFF setpoint. For emptying alarm, the setpoints
must be entered as negative values.
Page 40
MultiRanger 100/200 – INSTRUCTION MANUAL
alarm ON = LCD Icon ON = relay coil de-energized
pump ON = LCD Icon ON = relay coil energized
contact closed = LCD Icon ON = relay coil energized
Function
7ML19981FB05