Transducers

Warning: Hazardous voltage present on transducer terminals during
operation.
Run the transducer cable in a grounded metal conduit, separate from other
wiring (except TS-3 temperature sensor wiring, if applicable).
Notes:
Do not use coaxial cable because of electrical noise interference
Do not connect the shield and white transducer wires together; wire to separate
terminals
Disregard older transducer manuals that recommend these practices
A 0. 1 µF (100V or greater) capacitor is included with the MultiRanger for retrofitting old
MultiRanger Plus installations. Please see
retrofitting MultiRanger Plus Installations)

Relays

Relay contacts are shown in the de-energized position. All relays are handled identically
and can be configured as positive or negative logic using P118.
Relay Ratings
four Form A, NO
relays(1,2,4,5)
two Form C, NO or
NC relays (3,6)
5A at 250Vac, non-
inductive
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
white
TRANSDUCER TWO
black
white
TRANSDUCER ONE
black
MultiRanger 100/200 Installation (for
on page 247.
Power Failure
Relays 1, 2, 4, and 5 are
RELAY 1
normally open and will fail
in the normal state.
RELAY 2
Relays 3 and 6 can be
wired either normally open
or normally closed, and
RELAY 3
will fail in their de-
energized states.
RELAY 4
RELAY 5
RELAY 6