Selecting HI, LO, or HOLd
1.
Press FUNCTION
2.
Press ARROWS
3.
Press ENTER
Entering a Measurement
To enter a specific Failsafe Material Level within -50 to 150% of Span (P007), in Units
(P005).
Relay reaction
The way in which relay programming reacts to the failsafe level depends on P129 Relay
Failsafe (page 140). By default:
Alarm relays have P129 = OFF and so react to the Failsafe Material Level.
Control relays have P129 = dE and so de-energize the relay when the unit enters
Failsafe mode regardless of the Failsafe Material Level.
P072 Failsafe Level Advance
Sets the speed the MultiRanger advances to and returns from the Failsafe Material Level.
Primary Index
Values
Related

Relays (P100 to P119)

The MultiRanger has three or six relays (or digital outputs) used to control devices and
alarms. While the number of devices is limited by the relays, all control functions are
accessible through software and each parameter is indexed to the three or six relays.
Relay
See the
section on page 40.
Preset Applications (P100)
The MultiRanger makes standard applications easier to program by providing an
extensive list of presets.
Page 132
MultiRanger 100/200 – INSTRUCTION MANUAL
to display the Auxiliary Function symbol.
to scroll to the desired option.
to set the value.
Level
Advances to/from Failsafe Material Level as set by
1
* Restricted
P003, P700 and P701.
2
Immediate Failsafe Material Level assumed right away
Failsafe Level Advance is restricted, return is
3
Fast Back
immediate
P003 Maximum Process Speed
P070 Failsafe Timer
P071 Failsafe Material Level
P700 Max Fill rate
P701 Max Empty rate
7ML19981FB05