9410 series - User manual
Inputs/Outputs
Inputs/Outputs overview
Your meter has onboard digital Input/Output (I/O) which can be increased by adding optional
digital and analog I/O modules to expand your meter's I/O capabilities.
UNINTENDED OPERATION
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Do not use this device for critical control or protection of persons, animals, property, or
equipment.
Your meter base has:
• Three digital inputs
• One form A digital output
• Two energy pulsing LEDs (one visible, one infrared)
You can view information about your meter's I/O through the display and webpages, and
configure your meter's I/O using ION Setup.
NOTE: The digital outputs can handle voltages less than their specified maximum. For higher
voltage applications, use an external relay in the switching circuit.
Input/output ION modules
ION modules are used to configure your meter's digital or analog inputs/outputs (I/O).
You need to configure the following ION modules to use the meter's digital or analog I/O.
• Digital input: uses the Digital Input module, which tells the meter how to interpret incoming
signals.
• Digital output: uses one of three ION modules depending on the application.
• Analog input: uses the Analog Input module, which tells the meter how to interpret an
incoming analog voltage or current signal from transducers.
7EN05-0336-09
Digital Output module: Monitors a change of state to control relay operation via a
hardware output device.
Pulser module: Transfers high-speed pulses to a hardware pulse counting device that is
used to track energy usage.
Calibration Pulser module: Integrates instantaneous power inputs, then outputs high-
speed pulses to an LED that can be monitored for energy accuracy verification.
WARNING
Inputs/Outputs
121