Application Parameters

Volume (P050 to P055)

Use these parameters to enable the AiRanger DPL Plus to show readings based on
vessel volume (rather than level).
P050 Tank Shape
Enter the Tank Shape value matching the monitored vessel or wet well.
When Operation is level (P001 = 1), liquid (material) volume is calculated. Alternatively,
when Operation is space (P001 = 2), remaining vessel capacity is calculated. In RUN
mode, readings are displayed in percent of maximum volume. To convert readings to
volumetric units, see Maximum Volume (P051).
Primary Index
Values
7ML19981BD02
Transducer
#
Shape
0
1
2
3
4
5
6
AiRanger DPL Plus – INSTRUCTION MANUAL
volume calculation not required
*
(preset)
Flat Level Bottom
Cone/Pyramid Bottom
Parabola Bottom
Half Sphere Bottom
Flat Sloped Bottom
Flat Ends
Description
Page 33