Wiring
Check the condition of the bar terminal after crimping. Do not use a bar terminal of which the
crimping is inappropriate, or the face is damaged.
Fig. 3-10: Incorrectly crimped bar terminals
Wire Size [mm²]
1.25/1.5
0.75 (for two cables)
Tab. 3-12: Recommended bar terminals (Maker: Phoenix Contact Co., Ltd, as of Jan. 2017)
A bar terminal with an insulation sleeve compatible with MTW wire which has a thick wire insu-
lation
Applicable for terminal ABC
Wire Size [mm²]
0.3 to 0.75
Tab. 3-13: Recommended bar terminals (Maker: NICHIFU Co., Ltd, as of Jan. 2017)
FR-E700 SC EC/ENE
Damaged
With
Insulation Sleeve
0.3
AI 0,34-10TQ
0.5
Al 0.5-10WH
0.75
Al 0.75-10GY
1
Al 1-10RD
Al 1.5-10BK
Al-TWIN 2 × 0.75-10GY
Blade Terminal Poduct Number
BT 0.75-11
Crumpled tip
Bar Terminal Model
Without
Insulation Sleeve
A 0.75-10
A 1-10
A 1.5-10
AI 1.5-10BK/1000GB
Insulation Product Number
Control circuit specifications
Unstranded wires
Wires are not inserted
into the shell
Bar Terminal
Crimping Tool
For UL Wire
AI 0.5-10WH-GB
AI 0.75-10GY-GB
CRIMPFOX 6
AI 1-10RD/1000GB
Bar Terminal
Crimping Tool
VC 0.75
NH 69
I001985E