Mitsubishi Electric FR-E700 Instruction Manual page 458

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Special operation
NOTES
If the multi-speed (RH, RM, RL signal) or jog operation (jog signal) is entered with the X14 signal
on, PID control is stopped and multi-speed or jog operation is started.
If the setting is as follows, PID control becomes invalid. Pr. 79 "Operation mode selection" = "6"
(switchover mode). When the inverter is at a stop with Pr. 261 "Power failure stop selection"
selected.
Changing the terminal function using any of Pr. 178 to Pr. 184, Pr. 190 to Pr. 192 may affect the
other functions. Make setting after confirming the function of each terminal.
When PID control is selected, the minimum frequency is the frequency set in Pr. 902 and the maxi-
mum frequency is the frequency set in Pr. 903. (Pr. 1" Maximum frequency" and Pr. 2 "Minimum fre-
quency" settings are also valid.)
The remote operation function is invalid during PID operation.
When the control is switched to PID control during normal operation, the frequency command
value calculated by PID operation using 0 Hz as standard is used without the frequency during the
operation.
Frequency
command
PID action
6 - 304
PID set point
Frequency command
during normal operation
ON
Normal
PID
operation
operation
Operation when control is switched to
PID control during normal operation
Normal
operation
Parameter