Causes and corrective actions
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
Alarm
When an alarm occurs, the output is not shut off. You can also output an alarm signal by making pa-
rameter setting. (Set "98" in any of Pr. 190 to Pr. 192 "Output terminal function selection". Refer to sec-
tion 6.10.5).
Operation panel
indication
Name
Description
Check point
Corrective action
7 - 8
UV
Undervoltage
If the power supply voltage of the inverter decreases, the control circuit will not perform normal
functions. In addition, the motor torque will be insufficient and/or heat generation will increase.
To prevent this, if the power supply voltage decreases below about 230 V AC, this function stops
the inverter output and displays. An alarm is reset when the voltage returns to normal.
Check that the power supply voltage is normal.
Check that the power supply voltage is normal.
SA
Safety stop
Appears when safety stop function is activated (during output shutoff ).
Check if the shorting wire between S1 and PC or between S2 and PC is disconnected when not
using the safety stop function.
When not using the safety stop function, short across terminals S1 and P and across S2 and
SC with shorting wire for the inverter to run.
If SA is indicated when across S1 and SC and across S2 and PC are both shorted while using
the safety stop function (drive enabled), internal failure might be the cause.
Check the wiring of terminals S1, S2 and SC and contact your sales representative if the
wiring has no fault.
FN
Fan fault
For the inverter that contains a cooling fan, "FN" appears on the operation panel when the cool-
ing fan stops due to an alarm or different operation from the setting of Pr. 244 "Cooling fan oper-
ation selection".
Check the cooling fan for an alarm.
Replace the cooling fan.
FR-PU04
FR-PU07
FR-PU04
FR-PU07
FR-PU04
FN
FR-PU07
Troubleshooting