Special operation
Connection diagram
The following graphic shows a typical application:
Pr. 128 = 20
Pr. 182 = 14
Pr. 190 = 15
Pr. 191 = 14
Pr. 192 = 16
Forward rotation
Reverse rotation
Potentiometer
1 k , 1–2 W
(Set point
Fig. 6-152: Connection diagram in source logic
The power supply must be selected in accordance with the power specifications of the detector
used.
The used input signal terminal changes depending on the Pr. 178 to Pr. 184 "Input terminal
selection" setting.
The used output signal terminal changes depending on the Pr. 190 to Pr. 192 "Output terminal
selection" setting.
The AU signal need not be input.
6 - 298
Power
supply
PID control
selection
Setting
setting)
1 phase,
e. g. 230 V, 50 Hz
Pump
Upper limit
Lower limit
Power supply for OC outputs
Measured value 4–20 mA
Parameter
2 wire type
I002137C