Parameter
Ethernet IP filtering function (Pr. 837 to Pr. 843)
Set the IP address range for connectable network devices (Pr. 837 to Pr 843) to limit the connectable
devices. The IP address setting range depends on the settings in Pr. 838 and Pr. 841, Pr. 839 and Pr. 842,
and Pr. 840 and Pr. 843. (Either of the settings can be larger than the other in Pr. 838 and Pr. 841, Pr. 839
and Pr. 842, and Pr. 840 and Pr. 843.)
Example
Setting example 1:
In this case, the IP address range in which Ethernet communication is permitted is
"192.168.x (1 to 3).xxx (100 to 150)".
Ethernet IP address for
Filtering range setting for
the Ethernet IP address
Fig. 6-139: Setting example 1 for Ethernet IP filtering function
Example
Setting example 2:
In this case, the IP address range in which Ethernet communication is permitted is
"192.168.2.xxx (50 to 100)".
Filtering range setting for
Fig. 6-140: Setting example 2 for Ethernet IP filtering function
● When Pr. 837 to Pr. 840 = "0 (initial value)", the function is invalid.
● When Pr. 841 to Pr. 843 = "9999 (initial value)", the range is invalid.
FR-E700 SC EC/ENE
Pr. 837
192
filtering
The range is between the
values set in both
Pr. 837
Ethernet IP address for
192
filtering
the Ethernet IP address
Communication operation and setting
Pr. 838
Pr. 839
168
1
parameters.
Pr. 841
Pr. 842
9999
3
Pr. 838
Pr. 839
168
2
The range is between the
values set in both
parameters
Pr. 841
Pr. 842
9999
9999
Pr. 840
100
The range is between
the values set in both
parameters.
Pr. 843
150
Pr. 840
100
Pr. 843
50
I003110A
I003111A
6 - 287