Parameter overview
Parameter
Func-
Name
tion
65
Retry selection
Number of retries at alarm
67
occurrence
Retry waiting time
68
Retry count display erase
69
66
Refer to Pr. 22 and Pr. 23
67
—
–
Refer to Pr. 65
69
—
70
Refer to Pr. 30
Tab. 6-1:
Parameter overview (10)
6 - 10
Incre-
Initial
Setting
ments
Value
Range
1
0
0–5
0
1–10
1
0
101–110
0.1 s
1 s
0.1–360 s
1
0
0
Description
An alarm for retry can be selected.
No retry function
Set the number of retries at alarm
occurrence. An alarm output is not provided
during retry operation.
Set the number of retries at alarm
occurrence. (The setting value minus 100 is
the number of retries.) An alarm output is
provided during retry operation.
Set the waiting time from when an inverter
alarm occurs until a retry is made.
Clear the number of restarts succeeded by
retry.