Parameter
Setting the running frequency
The following program example changes the running frequency of station 1 inverter to 50.00 Hz.
● Set frequency: K5000 decimal
The reply code at the time of instruction code execution is set to D2.
(For information about the reply code (RWr2) refer to page 6-360.)
SM1536
SD1536.0
SD1540.0
(0)
M0
X20
(4)
M300
(8)
M301
X100D
(10)
M302
X100D
(17)
(23)
Fig. 6-183: Program example 7
NOTES
To continuously change the running frequency from the programmable controller
When the frequency (speed) setting completion (example: X100D) switches on, make sure that the
reply code in the remote register is 0000H and change the set data (example: W101) continuously.
Program example for writing data to E²PROM
Modify the program in fig. 6-183 as follows:
● Frequency setting command Y100D
● Frequency setting completion X100D
Inverter running
For E²PROM, write is made only once when Y100E is switched on.
If the set data is changed with Y100E on, it is not reflected on the inverter.
FR-E700 SC EC/ENE
Timing chart when writing to RAM
Y100D
W101
frequency
M0
Check the data link status of the station 1
PLS
M300
SET
M301
Write set frequency to RWw1.
MOV
K5000
W101
Turn off the frequency setting command RAM
SET
Y100D
(RY0D)
RST
M301
SET
M302
Read reply code (RWr2) to D2 when the frequency
MOV
setting completion (RX0D) turns on.
W2
D2
Turn off the frequency setting command RAM
RST
Y100D
(RY0D)
RST
M302
END
Y100E
X100E
Timing chart when writing to E²PROM
Y100E
W101
Inverter running
frequency
CC-Link IE Field Network Basic
I003136E
Reflect to the inverter when Y100E turns on
6 - 371