Mitsubishi Electric FR-E700 Instruction Manual page 156

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter overview
Parameter
Func-
Name
tion
3
Base frequency
Base frequency voltage
19
Second V/F (base frequency)
47
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting
6
(low speed)
24
Multi-speed setting
4 speed to 7 speed
27
232
Multi-speed setting
8 speed to 15 speed
239
Tab. 6-1:
Parameter overview (2)
6 - 2
Incre-
Initial
Setting
ments
Value
Range
0.01 Hz
50Hz
0–400 Hz
0–1000 V
0.1 V
8888
8888
9999
0–400 Hz
0.01 Hz
9999
9999
0.01 Hz
50Hz
0–400 Hz
0.01 Hz
30Hz
0–400 Hz
0.01 Hz
10Hz
0–400 Hz
0–400 Hz/
0.01 Hz
9999
9999
0–400 Hz/
0.01 Hz
9999
9999
Description
Set the frequency when the motor rated
torque is generated. (50Hz/60Hz)
Maximum inverter output voltage
95% of power supply voltage
Same as power supply voltage
Set the base frequency when the RT signal is
on.
Second V/F is invalid.
Set frequency when the RH signal is on.
Set frequency when the RM signal is on.
Set frequency when the RL signal is on.
Frequency from 4 speed to 15 speed can be
set according to the combination of the RH,
RM, RL and REX signals.
9999: not selected
Parameter
All
Para-
Para-
Para-
meter-
meter
meter
Copy
Clear
Refer
Clear
to
Page
✔: Enabled
—: Disabled
6-56
6-60

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720s sc ecFr-e720s sc eneFr-e740 sc ecFr-e740 sc ene

Table of Contents