Parameter
Example
Read the successful register start address and the number of successful accesses from the inverter.
Query message
Transaction
identifier
A given value is set.
Normal response (Response message)
Transaction
identifier
The values are the same as those in the query message.
Two successful reads of start address 41007 (Pr. 7) are returned.
FR-E700 SC EC/ENE
Protocol
Length field
identifier
H00
H00
H00
(8 Bits)
(8 Bits)
(8 Bits)
(8 Bits)
Protocol
Length field
identifier
H00
H00
H00
(8 Bits)
(8 Bits)
(8 Bits)
(8 Bits)
MODBUS®/TCP (FR-E700 SC ENE)
Unit
Func-
identi-
tion
fier
H02
HFF
H46
(8 Bits)
(8 Bits)
Unit
Func-
identi-
Starting address
tion
fier
H06
HFF
H10
H03
(8 Bits)
(8 Bits)
(8 Bits)
No. of points
HEE
H00
H02
(8 Bits)
(8 Bits)
(8 Bits)
6 - 343