Function assignment of external terminals
Setting
Terminal
Source
Sink
Logic
Logic
80
180
SAFE
81
181
SAFE2
90
190
Y90
91
191
Y91
93
193
Y93
95
195
Y95
96
196
REM
98
198
LF
99
199
ALM
9999
Tab. 6-31:
Output terminal function assignment (2)
Note that when the frequency setting is varied using an analog signal or the digital dial of the
operation panel, the output of the SU (up to frequency) signal may alternate on and off depend-
ing on that varying speed and the timing of the varying speed due to acceleration/deceleration
time setting. (The output will not alternate on and off when the acceleration/deceleration time
setting is "0 s".)
NOTES
The same function may be set to more than one terminal.
When the function is executed, the terminal conducts at the setting of any of "0" to "99", and does
not conduct at the setting of any of "100" to "199".
Changing the terminal assignment using Pr. 190 to Pr. 192 "Output terminal function selection"
may affect the other functions. Make setting after confirming the function of each terminal.
Do not assign signals which repeat frequent ON/OFF to A, B, and C. Otherwise, the life of the relay
contact decreases.
6 - 128
Function
Safety monitor output
Safety monitor output 2
Life alarm
Alarm output 3 (power-off signal)
Current average value monitor
signal
Maintenance timer signal
Remote Output
Minor fault output
Alarm output
No function
Operation
Output while safety stop func-
tion is activated.
The signal is output when no
internal safety circuit failure
(E.SAF, E.6, E.7, E.CPU) exists.
Output when any of the control
circuit capacitor, main circuit
capacitor and inrush current
limit circuit or the cooling fan
approaches the end of its ser-
vice life.
Output when an error occurs
due to the circuit failure or con-
nection alarm of the inverter.
Average current value and
maintenance timer value are
output as pulses. The signal can
not be set in Pr. 192 "ABC termi-
nal function selection".
Output when Pr. 503 rises to or
above the Pr. 504 setting.
Output to the terminal when a
value is set to the parameter.
Output when a minor fault (fan
failure or communication error
warning) occurs.
Output when the inverter's pro-
tective function is activated to
stop the output (major fault).
The signal output is stopped
when a reset turns on.
Parameter
Related Parameters Refer to
Page
3-24
3-24
Pr. 255–Pr. 259
6-319
6-130
Pr. 555–Pr. 557
6-324
Pr. 503, Pr. 504
6-323
Pr. 495–Pr. 497
6-135
6-234,
Pr. 121, Pr. 244
6-317
6-130