Operation selection at power failure
CAUTION:
E
Before activating the automatic restart after power failure function please make sure that this
mode is supported for the drive and permitted for your configuration.
When automatic restart after instantaneous power failure has been selected, the motor and
machine will start suddenly (after the reset time has elapsed) after occurrence of an instanta-
neous power failure. Stay away from the motor and machine. When you have selected automat-
ic restart after instantaneous power failure function, apply CAUTION stickers in easily visible
places.
When the start signal is turned off or is pressed during the restart cushion time after instanta-
neous power failure, deceleration starts after Pr. 58 "Restart cushion time" has elapsed.