Parameter
Operation continuation at instantaneous power failure function (Pr. 261 = 2)
When power is restored during deceleration after a power failure, acceleration is made again up to the
set frequency.
Fig. 6-85: Operation continuation at instantaneous power failure
When this function is used in combination with the automatic restart after instantaneous power fail-
ure function (Pr. 57 "9999"), deceleration can be made at a power failure and acceleration can be
made again after power restoration.
frequency
Fig. 6-86: Operation continuation at instantaneous power failure
NOTE
When operation continuation at instantaneous power failure function is used, keep the starting
signal (STF/STR) on even during instantaneous power failure. If the starting signal turns off during
instantaneous power failure, the inverter decelerates according to the deceleration time setting,
causing the motor to coast if enough regenerative energy is not obtained.
FR-E700 SC EC/ENE
Pr. 261 = 2
Power
supply
Output
frequency
Pr. 261 = 2, Pr. 57 9999
Power
supply
Output
During deceleration
at occurrence of
power failure
When power is restored during deceleration
During deceleration
at occurrence of
power failure
When used with automatic restart after instantaneous
power failure
During power failure
Operation selection at power failure
Reacceleration
Time
Deceleration time depends on Pr. 7 (Pr. 44).
Automatic restart after
instantaneous power failure
Time
Reset time + Pr. 57
I001176E
I001177E
6 - 167