Mitsubishi Electric FR-E700 Instruction Manual page 177

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
Parameter
Func-
Name
tion
Cooling fan operation
244
selection
245
Rated slip
Slip compensation time
246
constant
Constant-output region slip
247
compensation selection
Earth (ground) fault detection
249
at start
250
Stop selection
Tab. 6-1:
Parameter overview (23)
FR-E700 SC EC/ENE
Incre-
Initial
Setting
ments
Value
Range
0
1
1
1
0–50%
0.01%
9999
9999
0.01 s
0.5 s
0.01–10 s
0
1
9999
9999
0
1
0
1
0–100 s
1000–1100 s
0.1 s
9999
8888
9999
Description
Operates at power on
Cooling fan on/off control invalid
(The cooling fan is always on at power on.)
Cooling fan on/off control valid
Used to set the rated motor slip.
No slip compensation
Used to set the response time of slip
compensation. When the value is made
smaller, response will be faster. However, as
load inertia is greater, a regenerative
overvoltage (E.OV ) error is more liable to
occur.
Slip compensation is not made in the
constant output range (frequency range
above the frequency set in Pr. 3)
Slip compensation is made in the constant
output range.
Without ground fault detection
With ground fault detection
The motor is
coasted to a stop
STF signal:
when the preset
Forward rotation start
time elapses after
STR signal:
Reverse rotation start
the start signal is
turned off.
The motor is
coasted to a stop
STF signal:
(Pr. 250 1000) s
Start signal
after the start
STR signal:
signal is turned
Forward/reverse signal
off.
STF signal:
Start signal
When the start
STR signal:
signal is turned
Forward/reverse signal
off, the motor
STF signal:
decelerates to
Forward rotation start
stop.
STR signal:
Reverse rotation start
Parameter overview
All
Para-
Para-
Para-
meter-
meter
meter
Copy
Clear
Refer
Clear
to
Page
✔: Enabled
—: Disabled
6-317
6-43
6-173
6-105
6 - 23