MODBUS®/TCP (FR-E700 SC ENE)
Preset multiple registers (writing data to multiple holding registers) (H10 or 16)
● Data can be written to multiple holding registers.
● Query message
³
Transaction
identifier
H
(8 Bits)
(8 Bits)
● Normal response (Response message)
³
Transaction
identifier
H
(8 Bits)
(8 Bits)
● Query message setting
Message
³
Transaction identifier
·
Protocol Identifier
»
Length field
¿
Unit identifier
´
Function
²
Starting address
No. of points
º
Byte count
¾
Data
Tab. 6-128: Explanation of the query message
● Content of normal response
With a normal response, the contents in the response are the same as those in ³ to ¶ of the
query message.
6 - 340
·
»
Protocol
Length field
identifier
L
H
L
H
L
(8 Bits)
(8 Bits)
(8 Bits)
(8 Bits)
·
»
Protocol-
Length field
identifier
L
H
L
H
L
(8 Bits)
(8 Bits)
(8 Bits)
(8 Bits)
Description
The master adds the data for the purpose of transaction control.
The same data is returned in the response from the slave.
Fixed to 0. (When the slave receives data other than 0, it does not send the response
message.)
0 is returned in the response from the slave.
The data length from the unit identifier to the data is stored in byte.
Fixed to 255
Set H10.
Set the holding register address from which to start writing the data.
Starting address = start register address (decimal) - 40001
For example, when start register address 0001 is set, the data of holding register address
40002 is read.
Set the number of holding registers for writing data. Data can be read from up to 125
registers.
The setting range is H02 to HFA (2 to 250).
Set the value set in ¶ multiplied by 2.
The amount of data specified by ¶ is set. Write data is output Hi bytes first followed by Lo
bytes, and is arranged as follows: data of start address, data of start address+1, data of start
address+2, and so forth.
´
²
¿ Unit
Func-
Starting
identifier
tion
address
H10
H
L
(8 Bits)
(8 Bits)
(8 Bits)
(8 Bits)
¿
´
²
Unit
Func-
Starting
identifier
tion
address
H10
H
L
(8 Bits)
(8 Bits)
(8 Bits)
(8 Bits)
Parameter
º
Byte
No. of Points
Data
count
H
L
H
(8 Bits)
(8 Bits)
(8 Bits)
(8 Bits)
(8 Bits)
No. of Points
H
L
(8 Bits)
(8 Bits)
¾
...
L
(n × 2
× 8
Bits)