Parameter
Fig. 6-94: Signal adjustment of terminal 2
Fig. 6-95: Signal adjustment of terminal 4
There are three methods to adjust the frequency setting voltage (current) bias/gain:
● Method to adjust any point by application of voltage (current) to across the terminals 2-5 (4-5).
(Refer to page 6-187.)
● Method to adjust any point without application of a voltage (current) to across terminals 2-5 (4-5).
(Refer to page 6-188.)
● Adjusting only the frequency without adjusting the voltage (current).
(Refer to page 6-189.)
NOTE
When voltage/current input signal for terminal 4 was switched using Pr. 267 and voltage/current
input switch, perform calibration without fail.
FR-E700 SC EC/ENE
50 Hz
Bias
C2
(Pr. 902)
0
Frequency setting signal
0
0
C3 (Pr. 902)
50 Hz
Bias
C5
(Pr. 904)
0
Frequency setting signal
0
C6 (Pr. 904)
Frequency setting by analog input (terminal 2, 4)
Initial value
Gain Pr. 125
100%
5 V
10 V
C4 (Pr. 903)
Initial value
Gain Pr. 126
100%
20 mA
C7 (Pr. 905)
I001191E
I001191E
6 - 185