External operation
Possible faults:
The EXT lamp is not lit even when the PU/EXT key is pressed.
– Switchover of the operation mode with is valid when Pr. 79 = 0 (initial value).
● 50 Hz, 30 Hz and 10 Hz are not output from RH, RM and RL respectively when they are turned on.
– Check for the setting of Pr. 4, Pr. 5, and Pr. 6 once again.
– Check for the setting of Pr. 1 "Maximum frequency" and Pr. 2 "Minimum frequency" once again.
(Refer to section 5.1.4.)
– Check for the Pr. 79 setting once again. (Pr. 79 must be set to "0" or "2".) (Refer to section 5.1.6.)
– Check that Pr. 180 "RL terminal function selection" = "0", Pr. 181 "RM terminal function
selection" = "1", Pr. 182 "RH terminal function selection" = "2" and Pr. 59 "Remote function
selection" = "0". (All are initial values.)
● The RUN lamp is not lit.
– Check that wiring is correct.
– Check that "60" is set in Pr. 178 "STF terminal function selection" (or "61" is set in Pr. 179 "STR
terminal function selection"). (All are initial values.)
NOTE
External operation is fixed by setting "2" (external operation mode) in Pr. 79 "Operation mode
selection" when you do not want to take time pressing the PU/EXT key or when you want to use
the current start command and frequency command.