Communication operation and setting
Setting items and set data
After completion of parameter setting, set the instruction codes and data then start communication
from the computer to allow various types of operation control and monitoring.
No. Item
1 Operation Mode
2
Run command (extended)
3
Run command
Inverter status monitor
(extended)
4
Inverter status monitor
Tab. 6-78: Setting of the instruction codes and data (1)
6 - 256
Read/Write
Read
Write
Output frequency/
Read
speed
Output current
Read
Output voltage
Read
Special monitor
Read
Read
Special monitor selec-
tion No.
Write
Fault definition
Read
Write
Write
Read
Read
Instruction
Data Description
Code
H0000: Network operation
H7B
H0001: External operation
H0002: PU operation
HFB
H0000 to HFFFF:
Output frequency in 0.01 Hz increments
Speed increments 1/0.001 (when Pr. 37 = 0.01
to 9998)
When "0.01 to 9998" is set in Pr. 37 and "01" in
H6F
instruction code HFF, the increments change to
0.001 and the data format is E2.
When "100" is set in Pr. 52, the monitor value is
different depending on whether the inverter is
at a stop or running. (Refer to section 6.11.2.)
H0000 to HFFFF:
H70
Output current (hexadecimal) in 0.01 A incre-
ments
H0000 to HFFFF:
H71
Output voltage (hexadecimal) in 0.1 V
increments
H0000 to HFFFF:
Monitor data selected in instruction code HF3
H72
H01 to H3F:
H73
Monitor selection data
(Refer to Tab. 6-81 on page 6-260.)
HF3
H0000 to HFFFF:
Second fault in past
Fourth fault in past
H74 to H77
Sixth fault in past
Eighth fault in past
(Refer to Tab. 6-82 on page 6-261.)
You can set the control input commands such
HF9
as the forward rotation signal (STF) and reverse
rotation signal (STR).
HFA
(Refer to page 6-262 for details.)
You can monitor the states of the output sig-
H79
nals such as forward rotation, reverse rotation
and inverter running (RUN).
H7A
(Refer to page 6-262 for details.)
Parameter
Number
of Data
Digits
(Format)
4
(B, E/D)
4
(A, C/D)
4
6
(B, E,
E2/D)
4
(B, E/D)
4
(B, E/D)
4
(B, E/D)
6
(B, E2/D)
2
(B, E1/D)
2
(A1, C/D)
Latest alarm
Third fault in past
4
(B, E/D)
Fifth fault in past
Seventh fault in past
4
(A, C/D)
2
(A1, C/D)
4
(B, E/D)
2
(B, E1/D)