Siemens SIMATIC S7-300 Manual page 99

Fm 354 servo drive positioning module
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Message to the CPU (precondition: interrupt message activated (see Section 5.2)
No OB 82
exists
CPU
switches to
STOP
Diagnostic data
The following table contains the diagnostic information DIAGNOS-
TIC_INT_INFO in the user DB starting at address 72.
Table 6-4
4-byte
10-byte
FM 354 Servo Drive Positioning Module
OB 82
i t
Enters the diagnostic in-
formation in the diagnostic
buffer of the CPU (4 bytes)
and calls SFC 52
On operating error:
(addr. in user DB 80.7)
For further error specification by reading out DS 164 in OB 1
see example application 2
Diagnostic information
Data for-
Byte.Bit
mat
No.
0.0
Module/group disturbances (incoming and outgoing)
0.1
Internal error/HW error (group error bytes 2, 3)
0.2
External error
0.3
External channel error (group error byte 8)
0.6
Module not parameterized
1.0...3
Type class of module; for FM 354 = 08H
1.4
Channel information present
2.1
Communication disturbance (K bus)
2.3
Time monitoring actuated/Watchdog
2.4
Module internal power supply failed (NMI)
3.2
FEPROM error
3.3
RAM error
3.6
Process interrupt lost
4
FM Pos identifier (74H)
5
Length of diagnostic information (16)
6
No. of channels (1)
7
Channel error vector (1)
8.0
Cable break (incremental encoder)
8.1
Error in absolute encoder
8.2
Error pulse incr. or zero mark missing
8.3
Voltage monitoring - encoder
8.7
Operating error (see Chapter 11, Troubleshooting)
9...13
Free
Programming the FM 354
Diagnostic interrupt
Enters the diagnostic in-
formation in the user DB
starting at address 72 and
calls FC 4
Significance
OB 1
Calls FC
6
6-19