4.1.10.28

Forcing operating modes in the "Local" mode

Number of the
Feature2
Feature2 bit purpose
Specify whether forcing operating modes is possible in the "Local" mode.
The default setting is 0.
Bit = 0: In the "Local" mode, forcing operating modes is not possible.
Bit = 1: In the "Local" mode, forcing operating modes is possible.
4.1.10.29

Considering bad quality of automatic commands or external values

Number of the
Feature2
Feature2 bit purpose
Use this bit to consider the bad signal status (16#00 or 16#28) in the parameter for the
automatic commands or external values to move the block into the neutral position.
The default setting is 0.
Bit = 0: The bad signal status will not be considered.
Bit = 1: The bad signal status (
will be considered from the block. The block goes to a defined neutral position.
4.1.10.30

Separate interlock for each direction or position

Number of the
Feature2
Feature2 bit purpose
To enable the use of the "Separate interlock for each direction or position" function.
The default setting is 0.
Bit = 0: One interlock for each direction or position.
Bit = 1: Separate interlock for each direction or position.
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
bit: 8
bit: 10
bit: 16
or
) in the automatic commands or external values
16#00
16#28
Description of the blocks
4.1 Functions for all blocks
93