Conditions for changing the mode
Table 4- 93
No.
If
ModLiOp = 1
If the block is in local mode, no other mode can be activated for it.
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Conditions for changing the mode
Conditions
MANUAL (ON) → Out of service (Oos)
Via faceplate
(OosOp = 1)
on an edge transition
0 → 1
service mode)
Out of service (Oos) → MANUAL (ON)
Via faceplate
(ManModOp = 1)
Local → MANUAL
Via faceplate
(ManModOp = 1)
or
= 4
via
, if
LocalLi = 0
LocalSetting = 1, LocalSetting = 2
AUTOMATIC → MANUAL
Via faceplate
(ManModOp = 1)
via
if
ManModLi = 1
ModLiOp = 1
via
if
AutModLi = 0
ModLiOp = 1
MANUAL → AUTOMATIC
Via faceplate
(AutModOp = 1)
via
if
AutModLi = 1
ModLiOp = 1
Manual → Local
Via faceplate
(LocalOp = 1)
or
4
via
, if
LocalLi = 1
LocalSetting = 1, LocalSetting = 2
AUTOMATIC → Local
Via faceplate
(LocalOp = 1)
or
4
via
, if
LocalLi = 1
LocalSetting = 1, LocalSetting = 2
Local → AUTOMATIC
Via faceplate
(AutModOp = 1)
or
= 4
via
, if
LocalLi = 0
LocalSetting = 1, LocalSetting = 2
, the enabled operations for all mode changes will be deactivated.
if
or
ModLiOp = 0
from
if
OosLi,
Feature.Bit1 = 1
if
and
ModLiOp = 0
LocalSetting = 3
if
or
ModLiOp = 0
and
Feature.Bit4 =
and
Feature.Bit4 =
if
or
ModLiOp = 0
if
and
ModLiOp = 0
LocalSetting = 3
if
and
ModLiOp = 0
LocalSetting = 3
if
and
ModLiOp = 0
LocalSetting = 3
Description of the blocks
4.7 MMRevDhl motor block
(response for Out of
or
LocalSetting
0 (pushbutton mode) or
1 (switch mode)
or
LocalSetting =
or
LocalSetting =
or
LocalSetting
199