Selection Of Operating Mode - Siemens LMV36.520A1 Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

Building Technologies Division
Infrastructure & Citiies Sector
9

Selection of operating mode

To facilitate straightforward adaptation of the LMV36... to different types of burners, the
system offers automatic configuration of the operating mode. This means that – derived
from parameter 201 (fuel 0) / 301 (fuel 1) – the most important settings of configurations
relating to the operating mode are made automatically. Very often in that case, the only
manual settings to be made are those for the fuel-air ratio control system. After selection
of the operating mode, parameters that are not required will be hidden (e.g. oil
parameters when firing on gas).
No.
Parameter
Burner operating mode (fuel train, modulating / multistage, actuators, etc.)
-- = undefined (delete curves)
1 = G mod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2-stage
6 = Lo 3-stage
7 = G mod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
201
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod gas actuator only
20 = Gp1 mod gas actuator only
21 = Gp2 mod gas actuator only
22 = Lo mod oil actuator only
23 = HO mod with circulation
24 = HO 2-stage with circulation
25 = HO mod without circulation control
26 = HO 2-stage without circulation control
27 = HO 3-stage without circulation control
¹) Selected operating mode is not released for the basic unit.
With select: Error code 210 diagnostic code 0
Basic documentation LMV36...
9 Selection of operating mode
¹)
¹)
¹)
¹)
¹)
99/248
CC1P7544en
25.09.2013

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Agm60.4a9