Description of the blocks
4.7 MMRevDhl motor block
Monitoring of the starting and stopping characteristics for motors
The monitoring of the starting and stopping characteristics is implemented via the
MonTiDynamic
associated feedback value for a control signal, e.g.
this is not the case, the text "Feedback error" is displayed in the standard view of the
faceplate.
At the same time, an error message is output. The block then enters its neutral position. In
motors, this is always the stop state. The block signals this on the relevant output parameter
of the error message with 1, e.g. on the motor with
The parameters are set in seconds.
Note
The monitoring functions are functions of the block.
SIMOCODE pro nevertheless has its own functions for monitoring the on/off operations. You
can set these using the device parameters
time
The monitoring functions of the block can come into conflict with monitoring functions
configured in SIMOCODE pro under certain conditions.
Monitoring of the running characteristics for motors
The monitoring of the running characteristics is implemented via the
The monitoring time states the period in which the feedback value can change its value
quickly without an error message being output.
Example: A running motor with the feedback via the
should be static in accordance with the control, but may change its value within the
monitoring time.
If change of the
text will be displayed in the standard view of the faceplate.
At the same time, an error message is output. The block then enters its neutral position. For
motors, this is always the stop state. The block signals this on the relevant output parameter
of the error message with 1, e.g. on the motor with
The parameters are set in seconds.
Note
The monitoring functions are functions of the block.
SIMOCODE pro nevertheless has its own functions for monitoring the switching state of the
motor. You can set these using the device parameters
Feedback time
The monitoring functions of the block can come into conflict with monitoring functions
configured in SIMOCODE pro under certain conditions.
208
and
MonTiDyStop
.
parameter is longer than the monitoring time, the "Runtime error"
FbkStart
.
parameter. The monitoring time states the period in which the
FbkFwd
MonDynErr = 1
Motor control → Control function → Execution
FbkFwd
MonStaErr = 1
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
must be present in the motor. If
.
MonTiStatic
input parameter. This parameter
.
Motor control → Control function →
SIMOCODE pro PCS 7 Library V9.0
parameter.