"Interlock active" output via the LockAct parameter
The
parameters:
Intlock
Permit
Protect
Trip
The
acknowledgments have been acknowledged.
You can bypass the interlock using
also makes
How the signal status affects the interlocks
There are three ways in which the signal status affects the interlocks:
No.
1
2
3
Reference
MMRevDhl - Standard (Page 223)
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
parameter is always set automatically if an interlock is set in the following
LockAct
parameter if the interlock is canceled and the interlocks that require
LockAct = 0
.
LockAct = 0
Icon
Signal status
Simulation (16#60):
"bad, device-related" (16#28) or " bad, process-related" (16#00)
→ The signal status is used to activate the motor to stop.
Signal status ≠ Simulation, "bad, device-related" and " bad, process-
related"
→ No change in the block
in local mode and during simulation. This
BypProt = 1
If the interlock signal with the status 16#60 brings about a cancela-
tion of the interlock, this is processed as a bypass of the interlock in
the block.
If the interlock signal with status 16#60 does not bring about a can-
celation of the interlock, this is processed in the block as simulation.
Description of the blocks
4.7 MMRevDhl motor block
211