Table C‐3. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
DD_REVISION
PROFILE
PROFILE_REVISION
EXECUTION_TIME
NUMBER_OF_PARAMETERS
ADDRESS_OF_VIEW_1
NUMBER_OF_VIEWS
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Target Mode
TARGET_MODE
Index
RO /
Mode
Number
RW
0.7
Octet 1:
Number of PA profiles
within PI Profile Class. Set
to 0x40.
Octet 2:
0x01: Class A, all standard
params have their own
memory place.
0x02: Class B, all standard
params have their own
0.8
memory place.
0x81: Class A, all standard
params in 1 memory
place.
0x82: Class B, all standard
params in 1 memory
place.
253: Manufacturer
specific block structures
Octet 1:
Number before the
decimal point.
0.9
Octet 2:
Number after the decimal
point.
0.10
0.11
Octet 1 (MSB):
Slot
0.12
Octet 2 (LSB):
Index of View_1
parameter for access.
0.13
1
RO
0 to 65535
2
RW
ALL
3
RW
ALL
4
RW
ALL
0 to 255
7: OOS
5
RW
ALL
3: AUTO
Range
Default Value
0
0x4002
0x0302
0
0x86
0x0896
0x01
0
NULL
0
0
7
Blocks— Transducer Block
Protect
Description
Category
Data Type: Unsigned16
Data Type: Octet String
Profile Class given by PI, and
description of profile.
Data Type: Unsigned16
Profile revision used for this device.
Data Type: Unsigned16
Number of used parameters in the
block.
Data Type: Unsigned16
Address of View 1 parameter, see
table C‐4.
Data Type: Unsigned8
Number of view objects of the block.
Data Type: Uint16
The revision level of the static data.
Increments by one each time a static
N/A
parameter changes, or a change of a
table is accepted. Reset to 0 in case
of a cold start (ie if FACTORY_RESET
= 1 is set). Set to 1 if overflow.
Data Type: String
SETUP
The user description of the intended
application of the block.
Data Type: Uint16
User-specified value used in
SETUP
configuration or diagnostics as a key
in sorting block information.
Data Type: Uint8
The identification number of the
plant unit. This information may be
SETUP
used in the host for sorting alarms or
events generated by blocks.
Data Type: Uint8
N/A
The requested block mode.
June 2017