Blocks— Physical Block
June 2017
Table C‐1. Physical Block Parameter Definitions
Label
PARAMETER_NAME
DIAGNOSIS
76
Index
RO /
Mode
Number
RW
Octet 1
0-7: Reserved, set to 0
Octet 2
0-2: Reserved, set to 0
3: DIA_WARMSTART -
set after power up or
after executing
FACTORY_RESET =
2506 (A)
4: DIA_COLDSTART -
Set after executing
FACTORY_RESET = 1
(A)
5: DIA_MAINTENANCE
- Maintenance
required (R)
6: Reserved, set to 0
7: IDENT_NUMBER_
VIOLATION - set if
Ident_Number of the
running cyclic data
transfer and the value
13
RO
of IDENT_NUMBER_
SELECTOR does not
match. If IDENT_
NUMBER_SELECTOR =
127 then this bit is
cleared (R)
Octet 3
0: DIA_
MAINTENANCE_ALARM
- Failure of device (R)
1: Reserved, set to 0
2: DIA_FUNCTION_
CHECK - Device is in
function check mode,
simulation or local
control (R)
3: Reserved, set to 0
4-7: Reserved, set to 0
Octet 4
0 - 6: Reserved
7: DIAGNOSIS_
EXTENSION available.
(R)
Initial
Valid Range
Value
0
Instruction Manual
D103563X012
Description
Data Type: Octet String
Used for all configuration, hardware, connection
failure or system problems in the device. If in
CONDENSED mode, not more than 1 bit is to be
set for a single diagnostic event. Only
CONDENSED mode is supported here.
(R): Indication remains active as long as the alert
is active
(A): Indication is set within 10s, and will be
cleared not later than 10s after the action is
completed