Table 3‐2. Gain Values for Preselected Travel Tuning Sets
Tuning Set
Travel Proportional Gain
C
D
E
F
G
H
I
J
K
L
M
X (Expert)
Note
Use Expert tuning if standard tuning has not achieved the desired results.
Table 3‐3 provides tuning set selection guidelines for Fisher and Baumann™ actuators. These tuning sets are
recommended starting points. After you finish setting up and calibrating the instrument, you may have to select either
a higher or lower tuning set to get the desired response.
For an actuator not listed in table 3‐3, you can estimate a starting tuning set by calculating the casing or cylinder
volume. Then, find an actuator in table 3‐3 with the closest equivalent volume and use the tuning set suggested for
that actuator.
Travel Velocity Gain
4.4
4.8
5.5
6.2
7.2
8.4
9.7
11.3
13.1
15.5
18.0
User Adjusted
Travel Minor Loop Feedback Gain
3.0
3.0
3.0
3.1
3.6
4.2
4.8
5.6
6.0
6.0
6.0
User Adjusted
35
35
35
35
34
31
27
23
18
12
12
User Adjusted
Configuration
June 2017