Table C‐3. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
Travel Pressure Control
TVL_PRESS_CONTROL
Travel/Pressure Select
TVL_PRESS_SELECT
Travel/Pressure State
TVL_PRESS_STATE
Basic Setup
BASIC_SETUP
Actuator Style
ACTUATOR_STYLE
Zero Power Condition
ZERO_PWR_COND
Travel Sensor Motion
TRAVEL_SENSOR_MOTION
Feedback Connection
FEEDBACK_CONN
Relay Type
RELAY_TYPE
Maximum Supply Pressure
MAX_SUPP_PRESS
Pressure Range Hi
PRESS_RANGE_HI
Pressure Range Lo
PRESS_RANGE_LO
Travel Tuning Set
TVL_TUNING_SET
Pressure Tuning Set
PRESS_TUNING_SET
TRAVEL_CAL
Index
RO /
Mode
Number
RW
88
1=Travel
2=Pressure
88.1
RW
ALL
3=TVL/PRESS Auto Recv
4=TVL/PRESS Man Recv
1=Travel
88.2
RO
N/A
2=Pressure
89
1=Spring & Diaphragm
2=Piston‐Dbl w/o Spring
89.1
RW
OOS
3=Piston‐Dbl w/Spring
4=Piston Sgl w/Spring
1=Valve Closed
89.2
RW
OOS
2=Valve Open
1 = Counter Clockwise /
89.3
RW
OOS
Towards Top of
Instrument
0x40-0x7F = SensorX
89.4
RW
OOS
1=Relay A or C‐‐Double or
Single Direct
2=Relay B‐‐Single Reverse
5=Relay C‐Special App.
‐‐Single Direct
6=Relay B‐Special App.
‐‐Single Reverse
9=Lo‐Bleed Relay A or
C‐‐Double or Single
89.5
RW
OOS
Direct
10=Lo‐Bleed Relay B‐‐
Single Reverse
13=Lo‐Bleed Relay C‐
Special App.‐‐Single
Direct
10=Lo‐Bleed Relay
B‐Special App.‐-Single
Reverse
> 0, < = 150
89.6
RW
ALL
> 0, < = 150
89.7
RW
OOS
> = 0, < = 150
89.8
RW
OOS
1=B, 2= C, ...12=M
89.9
RW
ALL
23=X
1=B, 2=C, ...12= M
89.10
RW
ALL
23=X
90
Range
Default Value
1
N/A
1
1
1
0x40
1
35 psig
15.0 psig
3.0 psig
2
2
Blocks— Transducer Block
Protect
Description
Category
Data Type: Enum
SETUP
Selects whether travel sensor or port
A pressure is used for feedback.
Data Type: Enum
N/A
Indicates which sensor is used for
feedback.
SETUP
Data Type: Enum
Data Type: Enum
Identifies whether the valve is open
SETUP
or closed when instrument power is
lost.
SETUP
Data Type: Enum
SETUP
Data Type: Enum
Data Type: Enum
Note:
SETUP
Bit 0: Direct
Bit 1: Reverse
Bit 2: Special App
Bit 3: Lo-Bleed
SETUP
Data Type: Float
Data Type: Float
Defines pressure corresponding to
SETUP
max pressure in pressure control
mode.
Data Type: Float
Defines pressure corresponding to
SETUP
minimum pressure in pressure
control mode.
Data Type: Enum
SETUP
Letter (B through M or X)
Data Type: Enum
SETUP
Letter (B through M or X)