Fisher FIELDVUE DVC6200p Instruction Manual page 144

Digital valve controller
Hide thumbs Also See for FIELDVUE DVC6200p:
Table of Contents

Advertisement

Blocks —Logbook Function Block
June 2017
Table C‐14. Logbook Function Block Parameter Definitions
Label
PARAMETER_NAME
STATUS
SIZE_OF_ENTRIES
NUMBER_OF_ENTRIES
TURN_NUMBER
NEWEST_ENTRY
Type
Value
Active
Time
OLDEST_ENTRY
Type
Value
Active
Time
142
Index
RO /
Block
Number
RW
Mode
0: Reserved
1: NO_INIT
2: IDLE
10
RO
N/A
3: RUNNING
4-127: reserved
128-255: manufacturer
specific
11
RO
N/A
12
RO
N/A
13
RO
N/A
Default Value: Should
point to a non-existent
DS-62 entry with the
14
following values:
Status_Class = 0
Logbook_Entry = TRUE
Output_Reference = 0
14.1
Supervision = 0
Text = "Empty Logbook"
Status_Class definition:
1: Failure
RO
N/A
2: Maintenance Required
3: Function Check
14.2
4: Limits
5: Advisory
14.3
14.4
Default Value: Should
point to a non-existent
DS-62 entry with the
15
RO
N/A
following values:
Status_Class = 0
Logbook_Entry = TRUE
Output_Reference = 0
15.1
Supervision = 0
Text = "Empty Logbook"
Status_Class definition:
1: Failure
2: Maintenance Required
15.2
3: Function Check
4: Limits
5: Advisory
15.3
15.4
Range
Initial Value
3
260
0
0
255
0
FALSE
0
255
0
FALSE
0
Instruction Manual
D103563X012
Description
Data Type: Unsigned8
Contains the state of the function which is
currently executed or presents the result of
the execution.
Data Type: Unsigned16
Shows the number of different entries which
the Logbook can take up at the same time.
Data Type: Unsigned16
Contains the actual number of entries in the
Logbook.
Data Type: Unsigned16
Counts how many times the logbook has
completely been filled.
Data Type: DS-64
Contains the newest entry of the Logbook. As
long as no entries have been stored in the
Logbook, it shall point to a default value (see
default value for this parameter).
Data Type: Unsigned16
Contains the type of entry:
1-16 = Status information for status class n
255 = Binary Message
Data Type: Unsigned16
Depends on the value of Type:
Type = 1-16 --> Value = OR sum of the class
states of the specific class
Type = 255 --> Value = Number of Binary
Message
Data Type: Boolean
True = Binary Message becomes Active
False = Binary Message becomes Inactive
Data Type: BinaryDate The time the entry
was logged into the logbook.
Data Type: DS-64
Contains the oldest entry of the Logbook. As
long as no entries have been stored in the
Logbook, it shall point to a default value (see
default value for this parameter).
Data Type: Unsigned8
Contains the type of entry:
1-16 = Status information for status class n
255 = Binary Message
Data Type: Unsigned16
Depends on the value of Type:
Type = 1-16 --> Value = OR sum of the class
states of the specific class
Type = 255 --> Value = Number of Binary
Message
Data Type: Boolean
True = Binary Message becomes Active
False = Binary Message becomes Inactive
Data Type: BinaryDate The time the entry
was logged into the logbook.

Advertisement

Table of Contents
loading