Blocks— Transducer Block
June 2017
Table C‐3. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
Travel Count
TVL_COUNT
Travel Hi Calibration
TVL_HI_CAL
Travel Lo Calibration
TVL_LO_CAL
Travel Fac Hi
TVL_FAC_HI
Travel Fac Lo
TVL_FAC_LO
Travel IP Bias
TVL_IP_BIAS
Travel MLFB Bias
TVL_MLFB_BIAS
Last Calibration Type
TVL_CAL_TYPE
SELF_CALIB_PROG
TRAVEL_TUNE
Travel Integral Enable
TVL_INTEG_ENABLE
Travel Integral Limit Hi
TVL_INTEG_LIM_HI
Travel Integral Limit Lo
TVL_INTEG_LIM_LO
Travel Integral Dead Zone
TVL_INTEG_DEADZ
Travel MLFB Gain
TVL_MLFB_GAIN
PRESS_CAL
Supply Pressure Scale
SUPP_PRESS_SCALE
Supply Pressure Offset
SUPP_PRESS_OFFSET
Pressure A Scale
PRESS_A_SCALE
Pressure A Offset
PRESS_A_OFFSET
Pressure B Scale
PRESS_B_SCALE
Pressure B Offset
PRESS_B_OFFSET
Pressure IP Bias
PRESS_IP_BIAS
Pressure MLFB Bias
PRESS_MLFB_BIAS
PRESS_TUNE1
Pressure Cutoff Hi
PRESS_CUTOFF_HI
94
Index
RO /
Mode
Number
RW
90.1
RO
N/A
TVL_FAC_LO <= value <=
90.2
RW
OOS
TVL_FAC_HI
TVL_FAC_LO <= value <=
90.3
RW
OOS
TVL_FAC_HI
90.4
RO
N/A
90.5
RO
N/A
90.6
RW
OOS
0% - 100%
90.7
RW
OOS
0 - 100%
0: Not Calibrated
1: Single Point Calibration
90.8
RW
OOS
2: Auto Calibration
3: Manual Calibration
91
RO
92
1=Off
92.1
RW
ALL
2=On
92.2
RW
ALL
0% - 100%
92.3
RW
ALL
-100% - 0%
92.4
RW
ALL
0% - 2%
92.5
RW
ALL
0 <= value <= 32768
93
93.1
RW
OOS
0 to 32768.0
93.2
RW
OOS
0 to 16383
93.3
RW
OOS
0 to 32768.0
93.4
RW
OOS
0 to 16383
93.5
RW
OOS
0 to 32768.0
93.6
RW
OOS
0 to 16383
93.7
RW
OOS
0-100%
93.8
RW
OOS
0-100%
94
94.1
RW
ALL
-25 -125%
Range
Default Value
Set by Factory
Set by Factory
70%
50%
0
2
30%
-30%
0.25%
35
70%
50%
99.50%
Instruction Manual
D103563X012
Protect
Description
Category
Data Type: Unsigned16
Raw feedback from pot A/D.
Data Type: Unsigned16
CAL
Valve travel in A/D counts when
I/P drive is at maximum.
Data Type: Unsigned16
CAL
Valve travel in A/D counts when
I/P drive is at zero.
Data Type: Uint16
N/A
Maximum value of travel sensor
counts. Set at factory.
Data Type: Uint16
Minimum value of travel sensor
N/A
counts. Set at factory.
CAL
Data Type: Float
CAL
Data Type: Float
Data Type: Enum
CAL
What was the last calibration done?
Data Type: UINT8
N/A
Indicates the progress of self
calibration.
SETUP
Data Type: Enum
Data Type: Float
SETUP
Upper limit to the integrator output.
Data Type: Float
SETUP
Lower limit to the integrator output
Data Type: Float
Window around the Primary
SETUP
Setpoint in which the integral action
is disabled.
SETUP
Data Type: Float
CAL
Data Type: Float
CAL
Data Type: Uint16
CAL
Data Type: Float
CAL
Data Type: Uint16
CAL
Data Type: Float
CAL
Data Type: Uint16
CAL
Data Type: Float
CAL
Data Type: Float
Data Type: Float
SETUP
0.5% hysteresis on leaving cutoff.