Calibration
June 2017
Follow the prompts to automatically calibrate travel.
1. The auto calibration procedure is automatic. It is completed when the calibration menu shows the progress is 100%
complete.
During calibration, the instrument seeks the high and low end points. By searching for the end points, the
instrument establishes the limits of physical travel, i.e. the actual travel 0 and 100% positions. This also determines
how far the relay beam swings to calibrate the sensitivity of the beam position sensor.
2. Select the Calibration Type; Auto calibrate-Standard or Auto calibrate-Extended. Auto calibrate-Standard is used for
most applications. Actuators with boosters or special accessories may require Auto calibrate-Extended.
3. Enter the name of the person performing the calibration procedure.
4. Enter the location of the calibration procedure.
5. Enter the date of the calibration procedure.
6. Place the instrument in Auto mode for the valve to track input.
Manual Calibration
Select Manual Calibration on the Travel tab from the Configure > Calibrate menu.
Follow the prompts to manually calibrate travel.
Note
0% Travel = Valve Closed ; 100% Travel = Valve Open
1. From the adjustment menu, select the direction and size of change required to set the travel at 100% (move the
valve to any point between 10% and 90% open). Select the changes of 10%, 5%, 1%, -1%, -5% and -10%, respectively,
to choose the travel feedback movement. Select Next to implement the adjustment.
If another adjustment is required, repeat step 1. Otherwise, select Done and go to step 2.
2. From the adjustment menu, select the direction and size of change required to set the travel to 0% (move the valve
to close).
If another adjustment is required, repeat step 2. Otherwise, select Done and go to step 3.
3. Enter the name of the person performing the calibration procedure.
4. Enter the location of the calibration procedure.
5. Enter the date of the calibration procedure.
6. Place the Transducer Block Mode in Auto and verify that the travel properly tracks the input.

Relay

Select Relay on the A/B Pressure Sensor tab from the Configure > Calibrate menu. Follow the prompts to check relay
adjustment. Replace the digital valve controller cover when finished.
Note
Single-acting Relay B and C are not user‐adjustable.