Configuration
June 2017

Temperature Alerts

Temperature Hi
This alert is active if the temperature is greater than the Temperature Hi Alert Point.
D Temperature Hi Alert Point— active when the instrument temperature exceeds the Temperature Hi Alert Point.
Temperature Low
This alert is active if the temperature is lower than the Temperature Lo Alert Point.
D Temperature Lo Alert Point— active when the instrument temperature is lower than the Temperature Lo Alert Point.
Temperature Sensor
This alert is active if the Temperature Sensor reading is outside the functional range.
D Temperature—Degrees Fahrenheit or Celsius. The temperature is measured from a sensor mounted on the digital
valve controller's printed wiring board.

Electronics Alerts

Drive Current Alert
This alert is active when the difference between the expected Drive Current and the actual Drive Current has exceeded
the Drive Current Alert Time.
D Drive Current Alert Point— when the absolute difference between the Drive Current and Drive Signal exceeds the set
threshold for greater than the Drive Current Alert Time.
D Drive Current Alert Time— the maximum time, in seconds, that the Drive Current Alert Point can be exceeded
before the Drive Current Alert is active.
Drive Signal
The Drive Signal displays the commanded Drive Signal being sent to the I/P converter as a percentage of the maximum
drive.
This alert is active if one of the following conditions exist:
Where Zero Power Condition is defined as closed:
Drive Signal < 10% and Calibrated Travel > 3%
Drive Signal > 90% and Calibrated Travel < 97%
Where Zero Power Condition is defined as open:
Drive Signal < 10% and Calibrated Travel < 97%
Drive Signal > 90% and Calibrated Travel > 3%
32
Instruction Manual
D103563X012