Configuration
June 2017

Guided Setup

D Device Setup— This procedure, accessible from the Guided Setup tab, as shown in figure 3‐2, is used to configure
actuator and valve information, calibrate the valve assembly, and assign the tuning set for the valve assembly.
Figure 3‐2. Example of Typical Guided Setup Tab

Manual Setup

Manual Setup allows you to configure the digital valve controller to your application. Table 3‐1 lists the default settings
for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel
cutoffs and limits. You can also restart the instrument and set the protection.
Table 3‐1. Factory Default Settings
Setup Parameter
Travel Cutoff Hi
Travel Cutoff Lo
Travel Integral Gain
Travel Calibration Trigger
Travel Integral Enable
Travel Integral Limit Hi
Travel Integral Limit Lo
Travel Integral Deadzone
Pressure Cutoff Hi
Pressure Cutoff Lo
Pressure Integral Deadzone
Pressure Integral Hi Limit
Pressure Integral Lo Limit
Input Characterization
Shutdown Trigger
Shutdown Recovery
Output Block Timeout
14
Default Setting
99.5%
0.5%
0 repeats/min
No
On
30%
-30%
0.25%
99.5%
-0.5%
0.25%
50.0%
-50.0%
Linear
All Off
All Auto Recovery
600 sec
Instruction Manual