Blocks— Physical Block
June 2017
Table C‐1. Physical Block Parameter Definitions
Label
PARAMETER_NAME
Feature
FEATURE
SUPPORTED
ENABLED
COND_STATUS_DIAG
80
Index
RO /
Mode
Number
RW
26
Octet 1:
0: Diagnosis
Condensed_Status
supported
1: Diagnosis
Classic_Status
supported
2: Data exchange
26.1
RO
broadcast supported
3: MS1 application
relationship supported
4: Profisafe
communication
supported
5-7: Reserved
Octets 2-4: Reserved
Octet 1:
0: Diagnosis
Condensed_Status
enabled
1: Diagnosis
Classic_Status enabled
2: Data exchange
26.2
RO
broadcast enabled
3: MS1 application
relationship enabled
4: Profisafe
communication
enabled
5 - 7: Reserved
Octets 2-4: Reserved
0: Reserved
1: Condensed Status
27
RW
ALL
and Diagnosis
2 - 255: Reserved
Initial
Valid Range
Value
0x01000000
0x01000000
1
Instruction Manual
D103563X012
Description
Data Type: DS-68
Indicates optional features implemented in the
device and the status of these features, whether
supported or not supported.
Data Type: Unsigned8
Indicates / configures the type of status and
diagnostic currently being active in the device

Advertisement